Brainchild Electronic Co., Ltd
Product Name:
50 x 50 mm high performance fuzzy + PID controller
Features:
As a professional and experienced manufacturer, we supply high-performance and quality temperature controllers, which are also called temperature control, electronic temperature control, electronic temperature controller, and PID controller.
FEATURES
![]()
![]()
Specification:
-120 ~ 1000 °C Input 2 0-50.0 A 3.8-4 mA 0 V ±1.0 V 0.2 Vp-p
90 - 264 VAC, 47 - 63 Hz, 15VA, 7W maximum
11 - 26 VAC / VDC, SELV, Limited Energy, 15VA, 7W maximum
Input 1
Characteristics :
Resolution : 18 bits
(-184 ~ 1832 °F)
(-328 ~ 2498°F)
(-418 ~ 752°F)
(-148 ~ 1652 °F)
(32 ~ 3308 °F)
(200°C - 1820°C)
(32 ~ 3214 °F)
(32 ~ 3214 °F)
(-418 ~ 2372 °F)
(-328 ~ 1652 °F)
(DIN)
(-346 ~ 1292 °F)
(JIS)
(-328 ~ 1112 °F)
Sampling Rate : 5 times / second
Maximum Rating : -2 VDC minimum, 12 VDC maximum( 1 minute for mA input )
Temperature Effect : ±1.5 uV/ °C for all inputs except mA
input ±3.0 uV/ °C for mA input
Sensor Lead Resistance Effect :
T/C: 0.2uV/ohm
3-wire RTD: 2.6 °C/ohm of resistance difference of two leads
2-wire RTD: 2.6 °C/ohm of resistance sum of two leads 200nA
Common Mode Rejection Ratio ( CMRR ) : 120dB
Normal Mode Rejection Ratio ( NMRR ) : 55dB
Sensor Break Detection :
Sensor open for TC, RTD and mV inputs,
below 1 mA for 4-20 mA input,
below 0.25V for 1 - 5 V input, unavailable for other inputs.
Sensor Break Responding Time :
Within 4 seconds for TC, RTD and mV inputs,
0.1 second for 4-20 mA and 1 - 5 V inputs.
Resolution : 18 bits
Sampling Rate : 1.66 times / second
Maximum Rating : -2 VDC minimum, 12 VDC maximum
Emperature Effect : ±1.5uV/ °C for all inputs except mA
input ±3.0uV/ °C for mA input
Common Mode Rejection Ratio ( CMRR ): 120dB
Normal Mode Rejection Ratio ( NMRR ) : 55dB
Sensor Break Detection : Below 1 mA for 4-20 mA input,
below 0.25V for 1 - 5V input,
unavailable for other inputs.
Sensor Break Responding Time : 0.5 second
of Reading
±0.2A
Logic Low : -10V minimum, 0.8V maximum.
Logic High : 2V minimum, 10V maximum
External pull-down Resistance : 400 K maximum
External pull-up Resistance : 1.5 M minimum
Functions :
Select second set point and/or PID , reset alarm 1 and/or
alarm 2 , disable output 1 and/or output 2 , remote lockout.
Output 1 / Output 2
Relay Rating : 2A/240 VAC, life cycles 200,000 for resistive load
Pulsed Voltage : Source Voltage 5V, current limiting resistance 66 .
Linear Output Characteristics:
Resolution : 15 bits
Output Regulation : 0.01 % for full load change
Output Settling Time : 0.1 sec. ( stable to 99.9 % )
Isolation Breakdown Voltage : 1000 VAC
Temperature Effect : ±0.0025 % of SPAN / °C
Triac ( SSR ) Output
Rating : 1A / 240 VAC
Inrush Current : 20A for 1 cycle
Min. Load Current : 50 mA rms
Max. Off-state Leakage : 3 mA rms
Max. On-state Voltage : 1.5 V rms
Insulation Resistance : 1000 Mohms min. at 500 VDC
Dielectric Strength : 2500 VAC for 1 minute
DC Voltage Supply Characteristics (Installed at Output 2)
Alarm 1/ Alarm 2 ( Output 2 )
Alarm 1 Relay :
Form A or Form B for BTC-9300, Form C for BTC4300,
BTC-8300, 5V Logic output for BTC-2500 Max. Rating
2A/240VAC, life cycles 200,000 for resistive load.
Alarm 2 Relay :
Form A,Max. rating 2A/240VAC, life cycles 200,000 for resistive load.
Alarm Functions :
Dwell timer, Deviation
High / Low Alarm,
Deviation Band High / Low Alarm, PV1 High / Low Alarm,
PV2 High / Low Alarm, PV1 or PV2 High /Low Alarm,
PV1-PV2 High /Low Alarm, Loop Break Alarm,
Sensor Break Alarm.
Alarm Mode : Normal, Latching, Hold, Latching / Hold.
Dwell Timer : 0 - 6553.5 minutes
Data Communication
Interface : RS-232 ( 1 unit ), RS-485 ( up to 247 units )
Protocol : Modbus Protocol RTU mode
Address : 1 - 247
Baud Rate : 0.3 ~ 38.4 Kbits/sec
Data Bits : 7 or 8 bits
Parity Bit : None, Even or Odd
Stop Bit : 1 or 2 bits
Communication Buffer : 50 bytes
Analog Retransmission
Functions : PV1, PV2, PV1-PV2, PV2-PV1, Set Point,
MV1, MV2, PV-SV deviation value
Output Signal : 4-20 mA, 0-20 mA, 0-1V, 0-5V, 1-5V, 0-10V
Resolution : 15 bits
Accuracy : ±0.05 % of span ±0.0025 %/ °C
Load Resistance : 0 - 500 ohms ( for current output ),10 K ohm minimum ( for voltage
output )
Output Regulation : 0.01 % for full load change
Output Settling Time : 0.1 sec. (stable to 99.9 % )
Isolation Breakdown Voltage : 1000 VAC min.
Integral Linearity Error : ±0.005 % of span
Temperature Effect : ±0.0025 % of span/ °C
Saturation Low : 0 mA ( or 0V )
Saturation High : 22.2 mA ( or 5.55V, 11.1V min. )
Linear Output Range : 0 - 22.2mA(0-20mA or 4-20mA),
0 - 5.55V ( 0 - 5V, 1 - 5V ),
0 - 11.1 V ( 0 - 10V )
User Interface
Dual 4-digit LED Displays :
BTC-4300 Upper 0.55" ( 14mm )
Lower 0.4" ( 10 mm )
BTC-8300, BTC-9300 Upper 0.4" ( 10 mm )
Lower 0.31" ( 8 mm )
BTC-2500 0.4"(10mm)
Keypad : 3 keys
Programming Port : For automatic setup, calibration and testing
Communication Port : Connection to PC for supervisory control
Control Mode
Output 1 : Reverse ( heating ) or direct ( cooling )action
Output 2 : PID cooling control, cooling P band 1 ~ 255% of PB
ON-OFF : 0.1 - 55.6 ( °C ) hysteresis control ( P band = 0 )
P or PD : 0 - 100.0 % offset adjustment
PID : Fuzzy logic modified , Proportional band 0 ~ 500.0 °C ,
Integral time 0 - 1000 seconds , Derivative time 0 - 360.0 seconds
Cycle Time : 0.1 - 100.0 seconds
Manual Control : Heat (MV1) and Cool (MV2)
Auto-tuning : Cold start and warm start
Failure Mode : Auto-transfer to manual mode while sensor break or A-D converter damage
Ramping Control : 0 ~ 500.0 °C/minute or 0 ~ 500.0 °C/hour ramp rate
Sleep Mode : Enable or Disable
Ramping Control : 0 ~ 500.0 °C/minute or 0 ~ 500.0 °C/hour ramp rate
Power Limit : 0 - 100 % output 1 and output 2
Pump / Pressure Control : Sophisticated functions provided
Remote Set Point : Programmable range for voltage or current input
Differential Control : Control PV1 - PV2 at set point
Digital Filter
Function : First order
Time Constant : 0, 0.2, 0.5, 1, 2, 5, 10, 20, 30, 60 seconds programmable
Environmental & Physical
Operating Temperature : -10°C to 50°C
Storage Temperature : -40°C to 60°C
Humidity : 0 to 90 % RH ( non-condensing )
Insulation Resistance : 20 Mohms min. ( at 500 VDC )
Dielectric Strength : 2000 VAC, 50/60 Hz for 1 minute
Vibration Resistance : 10 - 55 Hz, 10 m/s² for 2 hours
Shock Resistance : 200 m/s² ( 20 g )
Moldings : Flame retardant polycarbonate
Dimensions :
BTC-4300 ---96mm(W) X 96mm(H) X 66mm(D), 53 mm depth behind panel
BTC-8300 ---48mm(W) X 96mm(H) X 80mm(D), 65 mm depth behind panel
BTC-9300 ---50.7mm(W) X 50.7mm(H) X 88.5mm(D), 75mm depth behind panel
BTC-2500 ---50mm(W) X 26.5mm(H) X 110.5 mm(D), 98.0 mm depth behind panel
Mounting:
BTC-4300 ---panel mount, cutout 92 X 92 ( mm )
BTC-8300 ---panel mount, cutout 45 X 92 ( mm )
BTC-9300 ---panel mount, cutout 45 X 45 ( mm )
BTC-2500 ---panel mount, cutout 45 X 22.2 ( mm )
Weight :
BTC-4300 --- 255 grams
BTC-8300 --- 220 grams
BTC-9300 --- 150 gram
BTC-2500 --- 120 grams
Approval Standards
Safety : UL 61010C-1 , CSA C22.2 No. 24-93 , EN61010-1 (IEC1010-1)
Protective Class :
BTC-8300, BTC-4300:
IP 20 housing and terminals with protective covers.
BTC-2500, BTC-9300:
NEMA 4X(IP65) front panel , IP 20 housing and terminals
EMC : EN61326
Other Description:
1 2 3 4 5 6
1 Power Input
4: 90 - 264 VAC, 47-63 HZ
5: 11 - 26 VAC or VDC, SELV, Limited Energy
2 Signal Input
1: Standard Input
Input 1-Universal Input
Thermocouple: J, K, T, E, B, R, S, N, L
RTD: PT100 DIN, PT100 JIS Current: 4 - 20mA, 0 - 20mA
Voltage: 0 - 1V, 0 - 5V, 1 - 5V, 0-10V
Input 2-CT: 0 - 50 Amp.AC
Current Transformer
Analog
Input: 4-20mA, 0-20mA, 0 - 1V, 0 - 5V, 1 - 5V, 0 - 10V
Input
3-Event Input (EI)
9: Special Order
3 Output 1
0: None
1: Relay rated 2A / 240VAC
2: Pulsed voltage to drive SSR, 5V / 30mA
3: Isolated 4 - 20mA / 0 - 20mA
4: Isolated 1 - 5V / 0 - 5V
5: Isolated 0 - 10V
6: Triac output 1A / 240VAC,SSR
C: Pulsed Voltage to drive SSR, 14V/40mA
9: Special order
4 Output 2 / Alarm 2
0: None
1: Form A relay 2A / 240VAC
2: Pulsed voltage to drive SSR, 5V / 30mA
3: Isolated 4 - 20mA / 0 - 20mA
4: Isolated 1 - 5V / 0 - 5V
5: Isolated 0 - 10V
6: Triac output, 1A / 240VAC, SSR
7: Isolated 20V / 25 mA DC Output Power Supply
8: Isolated 12V / 40 mA DC Output Power Supply
9: Isolated 5V / 80 mA DC Output Power Supply
C: Pulsed Voltage to drive SSR, 14V/40mA
A: Special order
5 Alarm 1
0: None
1: Form A relay 2A / 240VAC
2: Form B relay 2A / 240VAC
9: Special order
6 Communications
0: None
1: RS-485 interface
2: RS-232 interface
3: Retransmit 4 - 20 mA / 0 - 20 mA
4: Retransmit 1 - 5V / 0 - 5V
5: Retransmit 0 - 10V
9: Special order
This is the detailed information for 50 x 50 mm high performance fuzzy + PID controller, BTC-9300. The information includes model, name, description and specification for 50 x 50 mm high performance fuzzy + PID controller, BTC-9300. Related Keywords : High-performance PID controllers, PID controller. controller
Please send your Inquiries for 50 x 50 mm high performance fuzzy + PID controller, BTC-9300 to us. We will contact you soon. Please also check out the related product categories below.