Brainchild Electronic Co., Ltd
Product Name:
B41 Board PID
Features:
As a professional and experienced manufacturer, we supply high-performance and quality temperature controllers, which are also called temperature control, electronic temperature control, electronic temperature controller, and PID controller.
FEATURES
![]()
![]()
Specification:
-120 ~ 1000 °C 3.6-4 mA 0 V
90 - 250 VAC, 47 - 63 Hz, 12VA, 5W maximum
11 - 26 VAC / VDC, SELV, Limited Energy, 12VA, 5W maximum
Signal Input
Resolution : 18 bits
Sampling Rate : 5 times / second
Maximum Rating : -2 VDC minimum, 12 VDC maximum( 1 minute for mA input )
Temperature Effect : ±1.5 uV/ °C for all inputs except mA
input ±3.0 uV/ °C for mA input
Sensor Lead Resistance Effect :
T/C: 0.2uV/ohm
3-wire RTD: 2.6 °C/ohm of resistance difference of two leads
2-wire RTD: 2.6 °C/ohm of resistance sum of two leads
Burn-out Current : 200nA
Common Mode Rejection Ratio ( CMRR ) : 120dB
Normal Mode Rejection Ratio ( NMRR ) : 55dB
Sensor Break Detection :
Sensor open for TC, RTD and mV inputs,
Sensor short for RTD input,
below 1 mA for 4-20 mA input,
below 0.25V for 1 - 5 V input, unavailable for other inputs.
Sensor Break Responding Time :
Within 4 seconds for TC, RTD and mV inputs,
0.1 second for 4-20 mA and 1 - 5 V inputs.
Characteristics :
Output 1 / Output 2
(-184 ~ 1832 °F)
(-328 ~ 2498°F)
(-418 ~ 752°F)
(-148 ~ 1652 °F)
(32 ~ 3308 °F)
(200°C - 1820°C)
(32 ~ 3214 °F)
(32 ~ 3214 °F)
(-418 ~ 2372 °F)
(-328 ~ 1652 °F)
(DIN)
(-346 ~ 1292 °F)
(JIS)
(-328 ~ 1112 °F)
Relay Rating : 2A/240 VAC, life cycles 200,000 for resistive load
Pulsed Voltage : Source Voltage 5V, current limiting resistance 66Ω .
Linear Output Characteristics:
Linear Output
Resolution : 15 bits
Output Regulation : 0.02 % for full load change
Output Settling Time : 0.1 sec. ( stable to 99.9 % )
Isolation Breakdown Voltage : 1000 VAC
Temperature Effect : ±0.01 % of SPAN / °C
Triac ( SSR ) Output
Rating : 1A / 240 VAC
Inrush Current : 20A for 1 cycle
Min. Load Current : 50 mA rms
Max. Off-state Leakage : 3 mA rms
Max. On-state Voltage : 1.5 V rms
Insulation Resistance : 1000 Mohms min. at 500 VDC
Dielectric Strength : 2500 VAC for 1 minute
Alarm
Alarm Relay :Form C,Max. rating 2A/240VAC, life cycles 200,000 for resistive load.
Alarm Functions : Dwell timer,
Deviation
High / Low Alarm,
Deviation Band High / Low Alarm
Process High / Low Alarm
Alarm Mode : Normal, Latching, Hold, Latching / Hold.
Dwell Timer : 0.1 - 4553.6 minutes
Data Communication
Interface : RS-232 ( 1 unit ), RS-485 ( up to 247 units )
Protocol : Modbus Protocol RTU mode
Address : 1 - 247
Baud Rate : 2.4 ~ 38.4 Kbits/sec
Data Bits : 7 or 8 bits
Parity Bit : None, Even or Odd
Stop Bit : 1 or 2 bits
Communication Buffer : 160 bytes
Analog Retransmission
Output Signal : 4-20 mA, 0-20 mA, 0-1V, 0-5V, 1-5V, 0-10V
Resolution : 15 bits
Accuracy : ±0.05 % of span ±0.0025 %/ °C
Load Resistance : 0 - 500 ohms ( for current output ),10 K ohm minimum ( for voltage
output )
Output Regulation : 0.01 % for full load change
Output Settling Time : 0.1 sec. (stable to 99.9 % )
Isolation Breakdown Voltage : 1000 VAC min.
Integral Linearity Error : ±0.005 % of span
Temperature Effect : ±0.0025 % of span/ LC
Saturation Low : 0 mA ( or 0V )
Saturation High : 22.2 mA ( or 5.55V, 11.1V min. )
Linear Output Range :0-22.2mA(0-20mA or 4-20mA)
0-5.55V ( 0 - 5V, 1 - 5V )
0 - 11.1 V ( 0 - 10V )
User Interface
Dual 4-digit LED Displays :
Upper
0.55" ( 14mm )
Lower
0.4" ( 10 mm )
Keypad : 4 keys
Programming Port : For automatic setup, calibration and testing
Communication Port : Connection to PC for supervisory control
Control Mode
Output 1 : Reverse ( heating ) or direct ( cooling )action
Output 2 : PID cooling control, cooling P band 50 ~ 300% of PB, dead band -36.0
~ 36.0% of PB
ON-OFF : 0.1 - 90.0 ( °F ) hysteresis control ( P band = 0 )
P or PD : 0 - 100.0 % offset adjustment
PID : Fuzzy logic modified , Proportional band 0.1 ~ 900.0°F ,
Integral time 0 - 3600 seconds , Derivative time 0 - 360.0 seconds
Cycle Time : 0.1 - 90.0 seconds
Manual Control : Heat (MV1) and Cool (MV2)
Auto-tuning : Cold start and warm start
Failure Mode : Auto-transfer to manual mode while sensor break or A-D converter damage
Ramping Control : 0 ~ 900.0°F/minute or 0 ~ 900.0 °F/hour ramp rate
Digital Filter
Function : First order
Time Constant : 0, 0.2, 0.5, 1, 2, 5, 10, 20, 30, 60 seconds programmable
Environmental & Physical
Operating Temperature : -10°C to 50°C
Storage Temperature : -40°C to 60°C
Humidity : 0 to 90 % RH ( non-condensing )
Altitude : 2000m maximum
Pollution : Degree 2
Insulation Resistance : 20 Mohms min. ( at 500 VDC )
Dielectric Strength : 2000 VAC, 50/60 Hz for 1 minute
Vibration Resistance : 10 - 55 Hz, 10 m/s² for 2 hours
Shock Resistance : 200 m/s² ( 20 g )
EMC : EN61326
Other Description:
1 2 3 4 5 6 7
1 Power Input
4:
90 - 250 VAC, 47-63 HZ
5: 11 - 26 VAC or VDC, SELV, Limited Energy
2 Signal Input
1: Standard Input
Thermocouple: J, K, T, E, B, R, S, N, L
RTD: PT100 DIN, PT100 JIS
2: 0 - 60 mV
3: 0 - 1 V
4: 0 - 5 V
5: 1 - 5 V
6: 4 - 20 mA
7: 0 - 20 mA
8: 0 - 10V
9: Special Order
3 Output 1
0: None
1: Relay rated 2A / 240VAC
2: Pulsed voltage to drive SSR, 5V / 30mA
3: Isolated 4 - 20mA / 0 - 20mA
4: Isolated 1 - 5V / 0 - 5V
5: Isolated 0 - 10V
6: Triac output 1A / 240VAC,SSR
C: Pulsed voltage to drive SSR, 14V/40mA
9: Special order
4 Output 2
0: None
1: Form A relay 2A / 240VAC
2: Pulsed voltage to drive SSR, 5V / 30mA
3: Isolated 4 - 20mA / 0 - 20mA
4: Isolated 1 - 5V / 0 - 5V
5: Isolated 0 - 10V
6: Triac output, 1A / 240VAC, SSR
7: Isolated 20V / 25 mA DC Output Power Supply
8: Isolated 12V / 40 mA DC Output Power Supply
9: Isolated 5V / 80 mA DC Output Power Supply
C: Pulsed voltage to drive SSR, 14V/40mA
A: Special order
5 Alarm
0: None
1: Form C relay 2A / 240VAC
9: Special order
6 Communications
0: None
1: RS-485 interface
2:
RS-232 interface(not available for BTC-7100)
3:
Retransmit 4 - 20 mA / 0 - 20 mA
4:
Retransmit 1 - 5V / 0 - 5V
5:
Retransmit 0 - 10V
9: Special order
7 Options
0:
Panel mount IP50 standard
1:
Panel mount IP65 water resistant rubber installed
2:
DIN Rail mount with IP50 (for BTC-9100 only)
3:
DIN Rail mount with IP65 (for BTC-9100 only)
This is the detailed information for B41 Board PID, B41 Board PID. The information includes model, name, description and specification for B41 Board PID, B41 Board PID. Related Keywords : Board Type controller, PID controller
Please send your Inquiries for B41 Board PID, B41 Board PID to us. We will contact you soon. Please also check out the related product categories below.