| Product Name: |
for heater broken alarm |
| Description: |
It is a current transformer with wide measuring range 0 - 50Amp AC, to be used for heater broken protection with high-performance controllers BTC-2500, 9300, 8300 & 4300.
|
| Features: |
High Accuracy: ±2% of Reading ±0.2A
Wide Measuring Range: 0-50A ac
DC Voltage Output
Flexible lnstallation: DIN Rail Mount or wall(screw)Mount
Big Cable through Hole for Current Measurement
|
| Specification: |
Accuracy: ±2%of reading ±0.2A
Nominal Current: 0 ~ 50 A
Peak Current: 70 Aac 1minute
Output Impedance: 2.7 Kohms
Frequency Range: 47 ~ 63 Hz, sinewave
Breakdown Voltage: 2500 Vac, 1 minute
Isolation Resistance: >500 Mohm vs. 500 Vdc
Ambient Temperature: 0 ~ 60 C
Storage Temperature: -20 ~ 80 C
Mounting Method: DIN rail mount or Wall mount
Cable Size: 12.5mm diameter maximum
Dimension: 55mm(L) x 25.0mm(W) x 70.6mm(H)
Weight: 105 grams |
|
|