Brainchild Electronic Co., Ltd
Product Name:
96 x 96 mm Safety limit controller
Features:
As a professional and experienced manufacturer, we supply high-performance and quality temperature controllers, which are also called temperature control, electronic temperature control, electronic temperature controller, and PID controller.
Specification:
-120 ~ 1000 °C
90 - 250 VAC, 47 - 63 Hz, 10VA, 5W maximum
11 - 26 VAC / VDC, SELV, Limited Energy, 10VA, 5W maximum
Signal Input
Resolution : 18 bits
Sampling Rate : 5 times / second
Maximum Rating : -2 VDC minimum, 12 VDC maximum( 1 minute for mA input )
Temperature Effect : ±1.5 uV/ °C
input ±3.0 uV/ °C for mA input
Sensor Lead Resistance Effect :
T/C: 0.2uV/ohm
3-wire RTD: 2.6 °C/ohm of resistance difference of two leads
2-wire RTD: 2.6 °C/ohm of resistance sum of two leads
Burn-out Current : 200nA
Common Mode Rejection Ratio ( CMRR ) : 120dB
Normal Mode Rejection Ratio ( NMRR ) : 55dB
Sensor Break Detection :
Sensor open for TC, RTD and mV inputs,
Sensor short for RTD input,
below 1 mA for 4-20 mA input,
below 0.25V for 1 - 5 V input, unavailable for other inputs.
Sensor Break Responding Time :
Within 4 seconds for TC, RTD and mV inputs,
0.1 second for 4-20 mA and 1 - 5 V inputs.
Characteristics :
Output 1 / Output 2
(-184 ~ 1832 °F)
(-328 ~ 2498°F)
(-418 ~ 752°F)
(-148 ~ 1652 °F)
(32 ~ 3272 °F)
(200°C - 1800°C)
(32 ~ 3214 °F)
(32 ~ 3214 °F)
(-418 ~ 2372 °F)
(-328 ~ 1652 °F)
(DIN)
(-346 ~ 1292 °F)
(JIS)
(-328 ~ 1112 °F)
Relay Rating : 2A/240 VAC, life cycles 200,000 for resistive load
Pulsed Voltage : Source Voltage 5V, current limiting resistance 66Ω
Triac ( SSR ) Output
Rating : 1A / 240 VAC
Inrush Current : 20A for 1 cycle
Min. Load Current : 50 mA rms
Max. Off-state Leakage : 3 mA rms
Max. On-state Voltage : 1.5 V rms
Insulation Resistance : 1000 Mohms min. at 500 VDC
Dielectric Strength : 2500 VAC for 1 minute
Alarm
Alarm Relay :Form C,Max. rating 2A/240VAC, life cycles 200,000 for resistive load.
Alarm Functions : Dwell timer,
Deviation
High / Low Alarm,
Deviation Band High / Low Alarm
Process High / Low Alarm
Alarm Mode : Normal, Latching, Hold, Latching / Hold.
Dwell Timer : 0.1 - 4553.6 minutes
Data Communication
Interface : RS-232 ( 1 unit ), RS-485 ( up to 247 units )
Protocol : Modbus Protocol RTU mode
Address : 1 - 247
Baud Rate : 2.4 ~ 38.4 Kbits/sec
Data Bits : 7 or 8 bits
Parity Bit : None, Even or Odd
Stop Bit : 1 or 2 bits
Communication Buffer : 160 bytes
Analog Retransmission
Output Signal : 4-20 mA, 0-20 mA, 0-1V, 0-5V, 1-5V, 0-10V
Resolution : 15 bits
Accuracy : ±0.05 % of span ±0.0025 %/ °C
Load Resistance : 0 - 500 ohms ( for current output ),10 K ohm minimum ( for voltage
output )
Output Regulation : 0.01 % for full load change
User Interface
Dual 4-digit LED Displays :
Keypad : 4 keys
Programming Port : For automatic setup, calibration and testing
Communication Port : Connection to PC for supervisory control
Limit Control
High Limit, Low Limit and High/Low Limit programmable
Digital Filter
Function : First order
Time Constant : 0, 0.2, 0.5, 1, 2, 5, 10, 20, 30, 60 seconds programmable
Environmental & Physical
Operating Temperature : -10°C to 50°C
Storage Temperature : -40°C to 60°C
Humidity : 0 to 90 % RH ( non-condensing )
Altitude : 2000m maximum
Pollution : Degree 2
Insulation Resistance : 20 Mohms min. ( at 500 VDC )
Dielectric Strength : 2000 VAC, 50/60 Hz for 1 minute
Vibration Resistance : 10 - 55 Hz, 10 m/s² for 2 hours
Shock Resistance : 200 m/s² ( 20 g )
Moldings : Flame retardant polycarbonate
Dimensions : 96mm(W) X 96mm(H) X 65mm(D), 53 mm depth behind panel
Mounting : panel mount, cutout 92 X 92 ( mm )
Weight :250 grams
Event Input
Logic Low: Logic -10V minimum, 0.8V maximum.
Logic High: 2V minimum, 10V maximum.
Functions: Remote reset, remote lockout.
Approval Standards
Safety : UL 61010C-1 , CSA C22.2 No. 24-93 , EN61010-1 (IEC1010-1)
Protective Class :
IP65 front panel with
additional option,
IP50 front panel without
additional option,
all indoor use,
IP 20 housing and
terminals with protective cover.
EMC : EN61326
Other Description:
1 2 3 4 5 6 7 8
1 Power Input
4:
90 - 250 VAC, 47 - 63 HZ
5: 11 - 26 VAC or VDC, SELV, Limited Energy
2 Signal Input
1: Standard Input
Thermocouple:
J, K, T, E, B, R, S, N, L, C, P
RTD: PT100 DIN, PT100 JIS
2:
Voltage 0-1 V
3:
Voltage 0-10 V
4:
Current 0-20 mA
5: Voltage : 0-5 V
9:
Special Order
3 Output 1
0: None
1: Relay rated 2A / 240VAC
2:
Pulsed voltage to drive SSR, 5V / 30mA
6: Triac output 1A / 240VAC,SSR
C: Pulsed voltage to drive SSR, 14V/40mA
9: Special order
4 Output 2
0: None
1: Form A relay 2A / 240VAC
2:
Pulsed voltage to drive SSR, 5V / 30mA
6: Triac output, 1A / 240VAC, SSR
7: Isolated 20V / 25 mA DC Output Power Supply
8: Isolated 12V / 40 mA DC Output Power Supply
9: Isolated 5V / 80 mA DC Output Power Supply
C: Pulsed voltage to drive SSR, 14V/40mA
H:
Special order
5 Communications
0: None
1: RS-485 interface
2:
RS-232 interface
3:
Retransmit 4 - 20 mA / 0 - 20 mA
4:
Retransmit 1 - 5V / 0 - 5V
5:
Retransmit 0 - 10V
9: Special order
6 Options
0:
IP50 standard, non UL certified
1:
IP65 water resistant rubber installed, non UL certified
2:
IPx0 UL certified
7 , 8 Standard leave blank Special Order
AA-ZZ
This is the detailed information for 96 x 96 mm Safety limit controller, L41. The information includes model, name, description and specification for 96 x 96 mm Safety limit controller, L41. Related Keywords : Safety limit controller
Please send your Inquiries for 96 x 96 mm Safety limit controller, L41 to us. We will contact you soon. Please also check out the related product categories below.