| Product Name: |
96 x 96 mm limit controller |
| Description: |
The limit control LIMITROL L41 is an over temperature or a high limit safety device with a latching output that could remove the power while the process is in abnormal condition, for example the process higher than high limit set point or lower than the low limit set point.
|
| Specification: |
Power 90 - 250 VAC, 47 - 63 Hz, 10VA, 5W maximum
11 - 26 VAC / VDC, SELV, Limited Energy, 10VA, 5W maximum
Signal Input
Resolution : 18 bits
Sampling Rate : 5 times / second
Maximum Rating : -2 VDC minimum, 12 VDC maximum( 1 minute for mA input )
Temperature Effect : ±1.5 uV/ °C
input ±3.0 uV/ °C for mA input
Sensor Lead Resistance Effect :
T/C: 0.2uV/ohm
3-wire RTD: 2.6 °C/ohm of resistance difference of two leads
2-wire RTD: 2.6 °C/ohm of resistance sum of two leads
Burn-out Current : 200nA
Common Mode Rejection Ratio ( CMRR ) : 120dB
Normal Mode Rejection Ratio ( NMRR ) : 55dB
Sensor Break Detection :
Sensor open for TC, RTD and mV inputs,
Sensor short for RTD input,
below 1 mA for 4-20 mA input,
below 0.25V for 1 - 5 V input, unavailable for other inputs.
Sensor Break Responding Time :
Within 4 seconds for TC, RTD and mV inputs,
0.1 second for 4-20 mA and 1 - 5 V inputs.
Characteristics :
| Type |
Range |
Accuracy@
25 °C |
Input
Impedance |
| J |
-120 ~ 1000 °C
(-184 ~ 1832 °F)
|
±2 °C |
2.2MΩ |
| K |
-200 ~ 1370 °C
(-328 ~ 2498°F) |
±2 °C |
2.2MΩ |
| T |
-250 ~ 400°C
(-418 ~ 752°F) |
±2 °C |
2.2MΩ |
| E |
-100 ~ 900 °C
(-148 ~ 1652 °F) |
±2 °C |
2.2MΩ |
| B |
0 ~ 1800 °C
(32 ~ 3272 °F) |
±2 °C
(200°C - 1800°C) |
2.2MΩ |
| R |
0 ~ 1767.8 °C
(32 ~ 3214 °F) |
±2 °C |
2.2MΩ |
| S |
0 ~ 1767.8 °C
(32 ~ 3214 °F) |
±2 °C |
2.2MΩ |
| N |
-250 ~ 1300 °C
(-418 ~ 2372 °F) |
±2 °C |
2.2MΩ |
| L |
-200 ~ 900 °C
(-328 ~ 1652 °F) |
±2 °C |
2.2MΩ |
| PT100
(DIN) |
-210 ~ 700 °C
(-346 ~ 1292 °F) |
±0.4°C |
1.3KΩ |
| PT100
(JIS) |
-200 ~ 600 °C
(-328 ~ 1112 °F) |
±0.4°C |
1.3KΩ |
| mV |
-8 ~ 70mV |
±0.05% |
2.2MΩ |
| mA |
-3 ~ 27mA |
±0.05% |
70.5Ω |
| V |
-1.3 ~ 11.5V |
±0.05% |
650KΩ |
Output 1 / Output 2
Relay Rating : 2A/240 VAC, life cycles 200,000 for resistive load
Pulsed Voltage : Source Voltage 5V, current limiting resistance 66Ω
Triac ( SSR ) Output
Rating : 1A / 240 VAC
Inrush Current : 20A for 1 cycle
Min. Load Current : 50 mA rms
Max. Off-state Leakage : 3 mA rms
Max. On-state Voltage : 1.5 V rms
Insulation Resistance : 1000 Mohms min. at 500 VDC
Dielectric Strength : 2500 VAC for 1 minute
Alarm
Alarm Relay :Form C,Max. rating 2A/240VAC, life cycles 200,000 for resistive load.
Alarm Functions : Dwell timer,
Deviation
High / Low Alarm,
Deviation Band High / Low Alarm
Process High / Low Alarm
Alarm Mode : Normal, Latching, Hold, Latching / Hold.
Dwell Timer : 0.1 - 4553.6 minutes
Data Communication
Interface : RS-232 ( 1 unit ), RS-485 ( up to 247 units )
Protocol : Modbus Protocol RTU mode
Address : 1 - 247
Baud Rate : 2.4 ~ 38.4 Kbits/sec
Data Bits : 7 or 8 bits
Parity Bit : None, Even or Odd
Stop Bit : 1 or 2 bits
Communication Buffer : 160 bytes
Analog Retransmission
Output Signal : 4-20 mA, 0-20 mA, 0-1V, 0-5V, 1-5V, 0-10V
Resolution : 15 bits
Accuracy : ±0.05 % of span ±0.0025 %/ °C
Load Resistance : 0 - 500 ohms ( for current output ),10 K ohm minimum ( for voltage
output )
Output Regulation : 0.01 % for full load change
User Interface
Dual 4-digit LED Displays :
Keypad : 4 keys
Programming Port : For automatic setup, calibration and testing
Communication Port : Connection to PC for supervisory control
Limit Control
High Limit, Low Limit and High/Low Limit programmable
Digital Filter
Function : First order
Time Constant : 0, 0.2, 0.5, 1, 2, 5, 10, 20, 30, 60 seconds programmable
Environmental & Physical
Operating Temperature : -10°C to 50°C
Storage Temperature : -40°C to 60°C
Humidity : 0 to 90 % RH ( non-condensing )
Altitude : 2000m maximum
Pollution : Degree 2
Insulation Resistance : 20 Mohms min. ( at 500 VDC )
Dielectric Strength : 2000 VAC, 50/60 Hz for 1 minute
Vibration Resistance : 10 - 55 Hz, 10 m/s² for 2 hours
Shock Resistance : 200 m/s² ( 20 g )
Moldings : Flame retardant polycarbonate
Dimensions : 96mm(W) X 96mm(H) X 65mm(D), 53 mm depth behind panel
Mounting : panel mount, cutout 92 X 92 ( mm )
Weight :250 grams
Event Input
Logic Low: Logic -10V minimum, 0.8V maximum.
Logic High: 2V minimum, 10V maximum.
Functions: Remote reset, remote lockout.
Approval Standards
Safety : UL 61010C-1 , CSA C22.2 No. 24-93 , EN61010-1 (IEC1010-1)
Protective Class :
IP65 front panel with
additional option,
IP50 front panel without
additional option,
all indoor use,
IP 20 housing and
terminals with protective cover.
EMC : EN61326
|
| Other Description: |
L41 - □□□□□□□□
1 2 3 4 5 6 7 8
1 Power Input
4:
90 - 250 VAC, 47 - 63 HZ
5: 11 - 26 VAC or VDC, SELV, Limited Energy
2 Signal Input
1: Standard Input
Thermocouple:
J, K, T, E, B, R, S, N, L, C, P
RTD: PT100 DIN, PT100 JIS
2:
Voltage 0-1 V
3:
Voltage 0-10 V
4:
Current 0-20 mA
5: Voltage : 0-5 V
9:
Special Order
3 Output 1
0: None
1: Relay rated 2A / 240VAC
2:
Pulsed voltage to drive SSR, 5V / 30mA
6: Triac output 1A / 240VAC,SSR
C: Pulsed voltage to drive SSR, 14V/40mA
9: Special order
4 Output 2
0: None
1: Form A relay 2A / 240VAC
2:
Pulsed voltage to drive SSR, 5V / 30mA
6: Triac output, 1A / 240VAC, SSR
7: Isolated 20V / 25 mA DC Output Power Supply
8: Isolated 12V / 40 mA DC Output Power Supply
9: Isolated 5V / 80 mA DC Output Power Supply
C: Pulsed voltage to drive SSR, 14V/40mA
H:
Special order
5 Communications
0: None
1: RS-485 interface
2:
RS-232 interface
3:
Retransmit 4 - 20 mA / 0 - 20 mA
4:
Retransmit 1 - 5V / 0 - 5V
5:
Retransmit 0 - 10V
9: Special order
6 Options
0:
IP50 standard, non UL certified
1:
IP65 water resistant rubber installed, non UL certified
2:
IPx0 UL certified
7 , 8 Standard leave blank Special Order
AA-ZZ
|
|
|
| This is the specification for L41, 96 x 96 mm limit controller which includes model, name, description and specification for L41, 96 x 96 mm limit controller. Related Keywords : limit controller |
|
|